Insights

Notes on standalone power and WA’s energy transition

Occasional pieces written from the field. New articles are published on LinkedIn and listed here.

November 2026

Challenge Accepted: Design and Build a Standalone Power System That Replicates Grid Performance

The brief from a Western Australian utility was short. Design, fabricate, install and commission a standalone power system (SPS) that replicates the performance of the grid, so the utility can remove the long runs of ageing poles and wires that feed rural farms and households.

Short to write down. Hard to do.

Why the grid is a tough act to follow

At the edge of the network, a single farm can sit at the end of many kilometres of overhead line. That line is old, expensive to maintain and exposed to storms, fire and falling trees. An SPS at the property, with solar, battery storage and a backup generator, lets the utility take the line away altogether.

The customer should not notice the difference. The lights come on, the bore pump starts and the switchboard on the wall is the same one they have always had. Just as important, when something goes wrong inside the property, the protection has to work exactly as it would on the grid.

The hard part is fault current

On the grid, a short circuit draws a very large current from the network. That surge is what blows a fuse or trips a circuit breaker in a fraction of a second. It is how electrical protection in every home and shed has always worked.

Inverters do not behave that way. They are electronic devices that limit their own output, usually to not much more than their rated current. Put a conventional inverter system behind a standard household service fuse and a fault may never draw enough current to clear it quickly. Either the fault stays on, or the whole power system shuts itself down. Neither is acceptable to a utility.

So the requirement was specific. The SPS must supply enough fault current, for long enough, for the customer’s own protective device to clear a fault inside their premises within 0.4 seconds.

Getting the protection hierarchy right

Fault current is only half of it. The other half is order.

The utility’s requirement is that the consumer’s protection devices trip before the point of supply protective device, and before any protection device inside the SPS. A fault on one circuit should take out that circuit. A fault at the main switchboard should take out the main switch. The power system itself stays up, ready to supply again once the fault is fixed.

Behind that sits protection for every part of the system: the solar array, the battery bank, the inverters, the backup generator and the consumer supply. Fuses and circuit breakers are selected to work together, with backup protection at the critical points for both slow-rising faults and short circuits. And the hierarchy has to hold with built-in redundancy, not only when everything is running perfectly.

The answer is Modulus

Our answer is the Modulus Series, developed by CDI Energy in partnership with GTE Group.

Modulus-1 is a complete SPS built for Australian conditions. A factory-built cabinet houses the lithium iron phosphate battery storage, the modular inverters and the solar charge controllers. The backup generator sits outside the cabinet, within the same SPS enclosure as the solar array. The headline numbers are public on our fact sheet:

SpecificationModulus-1
AC output240 V, 50 Hz, 63 A, 12.9 kW nominal
Short-circuit current549 A for 0.4 seconds
Battery storage67.2 to 192 kWh, depending on model
Backup generatorUp to 40 kVA, automatic start
CabinetIP55, rated for -10 to 55 °C
Remote access4G/5G or Starlink
Design lifeMore than 15 years

The line that matters most is the second one. Modulus-1 delivers more than eight times its nominal current into a fault, for long enough to clear a standard 63 A service fuse or main breaker. That is what lets a utility treat the SPS like a grid connection, with the same customer switchboard, the same protection and the same expectations.

Each unit is assembled and tested before it leaves our Malaga workshop, then installed and commissioned on site. Once running, it operates on its own and is monitored remotely.

Built to be maintained, not just installed

Commissioning a system is one job. Keeping it running for 15 years at the end of a gravel road is another.

Across this industry, the systems that frustrate customers are the ones that are slow to repair when a part fails. A customer judges an SPS by what happens on that day.

Modulus was designed with that day in mind. Power conversion is handled by CE+T Sierra plug-in inverter modules, many small units working in parallel in place of one large inverter. The system carries built-in redundancy, so if one module fails the customer stays on supply and the system keeps its fault capability.

Replacing a failed module means sliding it out and plugging in a new one. The batteries and solar charge controllers are modular in the same way. Remote monitoring tells us which part needs attention before anyone leaves the workshop, so the right spare is on the ute and the repair is one visit.

What comes next: 125 A and 200 A

CDI Energy has now been engaged to expand the Modulus fleet with 125 amp and 200 amp output systems.

Larger connections mean larger farms and heavier loads. They also mean more fault current and a protection hierarchy that has to be proven again at each size. The principle does not change: if the poles and wires are coming down, what replaces them has to perform like the grid.

Challenge accepted, again.

Read more: Modulus Series brochure (PDF).

November 2026

Building Growth from Power Assets in Western Australia

Remote power in Western Australia used to be a simple business. Build a gas or diesel station at a mine or a town, sign a long contract, pass the fuel cost through and run the engines. Many of those stations are now 15 to 30 years old, their contracts are coming up for renewal, and several of the portfolios that own them are changing hands. Anyone buying, owning or lending against these assets is asking the same question: where does the growth come from?

My view, after 30 years across gas, upstream and now renewables, is that the growth is real but it is not in the engines.

Where the opportunity is

  • Hybrids are now the default. New mine power stations in WA combining wind, solar and several hours of battery storage are running at 80 per cent renewable and higher. Solar on its own typically settles between 30 and 60 per cent, and the last 20 points of renewable share cost more than the first 60. The skill is in sizing each site to its load, not chasing a headline number.
  • Investment earns a contract extension. A hybrid retrofit needs an extended period for payback, so the investment and the contract term have to be agreed together. Offering a renewable retrofit in exchange for a contract extension of around ten years lowers the customer’s fuel cost and emissions, and gives the owner of an ageing station a longer revenue base.
  • Utilities are buying renewables first. Regional town supply is being retendered on renewables-led terms, with gas kept for firming and long contracts backed by government. An incumbent wins by solving the utility’s firming and fuel security problem, not by defending the existing station.
  • Fuel prices are doing the selling. With diesel where it is, every remote customer has a reason to look at alternatives.

Where the risk is

  • The ore runs out before the contract does. The main threat to a mine power contract is the mine. A four-year reserve at a 30-year-old operation can be healthy if drilling keeps replacing what is mined. A ten-year reserve can be weak if the mine has never converted resource to reserve. You have to read the mine plan, not just count the years.
  • The customer you renew with is not the one who signed. Mining companies merge, sell assets and change strategy. Renewal intent sits with the site and its energy team, and no data room shows it.
  • Fuel supply chains are contracts with other people. Trucked LNG and remote gas depend on feed gas agreements, processing rights and roads that close in the wet. If those terms are shorter than the customer contracts, the margin is exposed.
  • Old engines carry deferred maintenance. Fleets of this age need steady overhaul spending, and that spending is easy to defer ahead of a sale.
  • Transition fuels have a window. Every point of renewable share at a site removes fuel volume. A long supply contract without a minimum take can deliver a fraction of what was modelled.
  • Delivery capacity is finite. Remote construction labour, grid-forming inverters and people prepared to live on site for weeks set how fast any of this can be built.

What builds growth

Three things, in my experience. Treat each contract renewal as a chance to offer investment in return for an extension. Fund a development team with a mandate to win new hybrid contracts, because that market has gone to the owners prepared to take development risk. And spend the diligence effort where the outcomes are binary: the largest utility contract and the two or three mine renewals that decide the case.

The businesses that grow from here will be the ones that stop seeing themselves as generators with a fuel contract and start acting as long-term energy partners to the mines and towns they supply.

October 2026

What it takes to install a standalone power system in a remote WA community

Most people picture a standalone power system as a few solar panels, a battery and a generator. The hardware is the easy part. A few things that actually decide whether the job goes well:

  • Logistics beat engineering. Sites are 850 to 1,100 km from the Malaga workshop at the end of unsealed roads that close when it rains. Forget something and it’s a week’s delay, not an afternoon’s.
  • The site is someone’s home. Talk to residents and community leaders early, keep switchovers short, leave the place tidier than you found it.
  • Weather dictates the programme. Pilbara heat, cyclone season and wet-season access windows set the schedule.
  • Commissioning is where reliability is won. Protection settings, generator cycling and remote monitoring get more testing time than anything else.
  • People make it work. Electricians and project managers happy to camp on site for weeks are rarer than good equipment.

Getting diesel out of remote communities is one of the cheapest wins in WA’s energy transition, and SPS is how it gets done.

Read on LinkedIn →